Middle East Contact Us English

200 kVA Canopied GHP Genset

Technical Data

200 kVA GENSET
Maximum Ambient (before de-rate)
Engine
Battery Voltage
Alternator
AVR
Voltage Range (50 hz)
Voltage Range (60 hz)
Circuit Breaker
No. of Poles
Rating
Load Terminals
UNIT
°C/°F
Cummins
Volts DC
Newage
-
Volts AC
Volts AC
Merlin Gerin
-
Amps
-
VALUE
36/97(50Hz) 36/97(60Hz)
6CTAA8.3G5
24
UCD274J13
MX 341
380-415
416-480
NS630N
4
630
M12 Bolts
FUEL CAPACITY
Gross
Usable
UNIT
Litres
Litres
VALUE
993
930
DIMENSIONS AND WEIGHT
Length
Width
Height
Weight (without fuel)
Weight (with fuel)
UNIT
Mtr/Ft
Mtr/Ft
Mtr/Ft
Kg
Kg
VALUE
3.985/13'1"
1.2/3'11"
2.472/9'0"
3800
4644
PREVENTATIVE MAINTENANCE
Type 'A' Service
Type 'B' Service
SERVICE INTERVAL
400 Hours
2000 Hours
FUEL CONSUMPTION
Standby/Fuel Stop
100% Prime Power
75% Prime Power
50% Prime Power
UNIT
Lt/hour
Lt/hour
Lt/hour
Lt/hour
VALUE
51.1(50Hz) 63.6(60Hz)
45.4(50Hz) 56.0(60Hz)
34.0(50Hz) 41.3(60Hz)
22.7(50Hz) 27.6(60Hz)
RUNNING HOURS (INTERNAL TANK)
100% Prime Power
75% Prime Power
50% Prime Power
UNIT
Hours
Hours
Hours
VALUE
20.5(50Hz) 16.6(60Hz)
27.4(50Hz) 22.5(60Hz)
41.0(50Hz) 33.7(60Hz)
NOISE LEVEL
Sound Pressure at 1Mtr
Sound Pressure at 7Mtr
Sound Pressure (EEC Std.)
UNIT
dBA
dBA
Lw
VALUE
78(50Hz) 80(60Hz)
70(50Hz) 73(60Hz)
-
EMISSIONS (TIER 2 COMPLIANT @ 100% LOAD)
NOx (Oxides of Nitrogen)
PM (Particular Matter)
CO (Carbon Monoxide)
HC (Hydrocarbons)
NOx + HC
TA-Luft 50 Hz(mg/nm3)
4000
130
650
150
-
EPA 60Hz(g/kWh)
6.4
0.2
3.5
-
6.4
CABLE RATING - 200 kVA, 288 AMP @ 400V
Size
Type
1x150mm2/phase
1 core

Loadbanks

AC loadbanks 600KW resistive only to 6MVA resistive and inductive in single units

All AC loadbanks controlled by the 'Sigma' computerized system

DC loadbanks ranging from 24 Volts/300 Amps to 500 Volts/1500 Amps

High and Low Voltage data capture capability

Sigma load control allows load steps down to 1KW/kVA

Applications in gas turbines testing, wind turbine commissioning, UPS testing, transformer testing

 

 

Transformers

Capacities ranging from 630 kVA to 6.3MVA in single units

Housed in custom designed 10' or 20' containers

Easily transportable by road, rail, sea or rail

Simple LV & HV connections for safe and easy installation

Over current and short circuit protection on HV Breaker

HV step-up capability above 25kV

Fuel Tanks

External tank in capacities ranging up to 20000 litres

Fully bunded to prevent leaks and hazards

Facilities uninterrupted running for extended periods

Fuel delivery connection at ground level to dreduce the need to work at height

Pneumatic level gauge

Audible alarm to provide over fill protection

Mechanical over fill protection

Lifting eyes for empty handling only

Cable

Single or four/five core for mobile service

Designed to withstand mechanical stress at site

Highly resistant to abrasion, fuel, oil and water

High current-carrying capacity