500 kVA Canopied GHP Genset

Technical Data

500 kVA GENSET
Maximum Ambient (before de-rate)
Engine
Battery Voltage
Alternator
AVR
Voltage Range (50 hz)
Voltage Range (60 hz)
Circuit Breaker
No. of Poles
Rating
Load Terminals
UNIT
°C/°F
Scania
Volts DC
Newage
-
Volts AC
Volts AC
Merlin Gerin
-
Amps
-
VALUE
35/90(50Hz) 38/100(60Hz)
DC16 45A
24
HC153 4E
MX 341
380-440
416-480
NS 1250N
4
1250
Busbar M12
FUEL CAPACITY
Gross
Usable
UNIT
Litres
Litres
VALUE
1397
1231
DIMENSIONS AND WEIGHT
Length
Width
Height
Weight (without fuel)
Weight (with fuel)
UNIT
Mtr/Ft
Mtr/Ft
Mtr/Ft
Kg
Kg
VALUE
5.16/16'9"
1.90/6'2"
2.56/8'4"
7800
8700
PREVENTATIVE MAINTENANCE
Type 'A' Service
Type 'B' Service
SERVICE INTERVAL
400 Hours
2400 Hours
FUEL CONSUMPTION
Standby/Fuel Stop
100% Prime Power
75% Prime Power
50% Prime Power
UNIT
Lt/hour
Lt/hour
Lt/hour
Lt/hour
VALUE
102.4(50Hz) 102.5(60Hz)
92.3(50Hz) 90.5(60Hz)
67.8(50Hz) 66.8(60Hz)
46.2(50Hz) 46.2(60Hz)
RUNNING HOURS (INTERNAL TANK)
100% Prime Power
75% Prime Power
50% Prime Power
UNIT
Hours
Hours
Hours
VALUE
13.3(50Hz) 13.6(60Hz)
18.2(50Hz) 18.4(60Hz)
26.6(50Hz) 26.6(60Hz)
NOISE LEVEL
Sound Pressure at 1Mtr
Sound Pressure at 7Mtr
Sound Pressure (EEC Std.)
UNIT
dBA
dBA
Lw
VALUE
75.8(50Hz) 74.6(60Hz)
69.0(50Hz) 66.2(60Hz)
-
EMISSIONS (TIER 2 COMPLIANT @ 100% LOAD)
NOx (Oxides of Nitrogen)
PM (Particular Matter)
CO (Carbon Monoxide)
HC (Hydrocarbons)
UNIT
g/kWh
g/kWh
g/kWh
g/kWh
VALUE
5.888(50Hz) 5.57(60Hz)
-(50Hz) 0.07(60Hz)
0.586(50Hz) 0.49(60Hz)
0.273(50Hz) 0.35(60Hz)
CABLE RATING - 500 kVA, 721 AMP @ 400V
Size
Type
2x240mm2/phase
1 core

Loadbanks

AC loadbanks 600KW resistive only to 6MVA resistive and inductive in single units

All AC loadbanks controlled by the 'Sigma' computerized system

DC loadbanks ranging from 24 Volts/300 Amps to 500 Volts/1500 Amps

High and Low Voltage data capture capability

Sigma load control allows load steps down to 1KW/kVA

Applications in gas turbines testing, wind turbine commissioning, UPS testing, transformer testing

 

 

Transformers

Capacities ranging from 630 kVA to 6.3MVA in single units

Housed in custom designed 10' or 20' containers

Easily transportable by road, rail, sea or rail

Simple LV & HV connections for safe and easy installation

Over current and short circuit protection on HV Breaker

HV step-up capability above 25kV

Fuel Tanks

External tank in capacities ranging up to 20000 litres

Fully bunded to prevent leaks and hazards

Facilities uninterrupted running for extended periods

Fuel delivery connection at ground level to dreduce the need to work at height

Pneumatic level gauge

Audible alarm to provide over fill protection

Mechanical over fill protection

Lifting eyes for empty handling only

Cable

Single or four/five core for mobile service

Designed to withstand mechanical stress at site

Highly resistant to abrasion, fuel, oil and water

High current-carrying capacity